Section 4

SECTION 400

STANDARD SERVICES

401 Availability of Service

Although the types of service listed below are generally available through the area served by DLPUD, service of the type requested by a Customer may not be available at the location where such service is desired, and in certain cases may be available only through special contractual arrangements and at the expense of the Customer. Each Customer will generally be allowed only one type of service and one point of connection for each location.

402 Secondary Service Voltages

The following types of secondary service are generally available to Customers served under DLPUD’s Standard Rate Schedules:

402.1 Single Phase Service

120/240 Volt, 3-Wire, Grounded Neutral. Generally available where the total load is less than 100 kVA.

402.2 Three Phase Service

1) 120/208Y Volt, 4-Wire, Grounded Neutral. Generally available where the total load is 75 kVA or greater for pad-mounted transformer service, or 45 kVA or greater for pole-mounted transformer service.
2) 120/240 Volt, Delta, 4-Wire, Grounded Neutral. Service provided only from pole-mounted transformer installations and only where installed capacity or current needs exist.
3) 240 Volt (and 480 Volt), Delta, 3-Wire. Service provided only from pole-mounted transformer installations and only where installed capacity or current needs exist.
4) 277/480Y Volt, 4-Wire, Grounded Neutral. Generally available where the total load is 75 kVA or greater for a pad-mounted transformer service.

403 Primary Service Voltages

Three-Phase, 12470/7200 Volt, 4-Wire, Grounded Neutral Service: Available only by special request where the total load is 300 kVA or greater.

404 Fault Current

It shall be the responsibility of the customer and/or electrical contractor to install proper over-current protective equipment.